This fixed speed ageing Booster set was in complete disrepair at a hotel in Brighton. The control panel had been exposed to the elements for many years and as such many components were no longer working. The diaphragm in the accumulator vessel had split so the pumps were running none stop. As a result, over time all of the pumps seized and burnt out one by one. Pressboost received an urgent callout to total water failure and managed to obtain and install a new pump that night to get water back on. Two weeks later we returned to site and installed a new 3 pump variable speed unit. The new unit has 3 much smaller accumulator vessels, 3 transducers and 3 inverters making the unit fail safe. We removed the plastic pipework and replaced with stainless steel and lagged the previously exposed pipework, we also installed bracketing for the wiring that previously hung free. This work was completed in an 8 hour window from 9am in the morning and the water had to be re-instated by 5pm that same evening …………………….. No pressure!